What size air compressor to blow out sprinklers

The air has to push water out at about the zone’s own flow, and compressors are rated in a different kind of CFM.

Short answer

Size it from your largest zone's flow. Pushing a 10 GPM zone out at 50 PSI at its design flow takes about 5.9 SCFM of free air, so a 20 to 30 gallon compressor does it comfortably and a 6 gallon pancake does it in short bursts with waits to refill. Never exceed 80 PSI on PVC pipe or 50 PSI on polyethylene.

See how much air your tank holds

From zone GPM to compressor CFM

Colorado State University Extension sizes the compressor by dividing the zone's flow in gallons per minute by 7.5, because a cubic foot holds about 7.5 gallons: its example zone of 20 GPM at 30 PSI needs 2.7 CFM. That is right as far as it goes, but it is cubic feet of air at the pressure in the pipe. Compressors are rated in SCFM, free air at atmospheric pressure, and air squeezed to 30 or 50 PSI takes up a fraction of its free volume. So the compressor has to deliver more than the simple rule says:

Free air (SCFM) needed to move a zone's design flow, by air pressure in the pipe
Zone flowAir volume (GPM ÷ 7.5)SCFM at 30 PSISCFM at 50 PSI
6 GPM0.82.43.5
8 GPM1.13.34.7
10 GPM1.34.15.9
12 GPM1.64.97.1
15 GPM2.06.18.8
20 GPM2.78.111.8

Matching the design flow is what keeps the heads popped up and the water moving out as a slug. With less air, CSU warns, the air rides over the top of the water and leaves it lying in the low spots, which is exactly where a freeze splits a pipe. Their rule of thumb: if the heads stay up and air keeps flowing after the water is out, the compressor is big enough.

Finding your zone's GPM

  • From the water meter: run one zone with nothing else on, read the meter, wait one minute, read it again. The difference is the zone's GPM.
  • From the heads: add up the flow of every nozzle on the zone from the manufacturer's nozzle chart.

Many meters read in cubic feet rather than gallons; multiply a cubic-foot reading by 7.48. Size the compressor for the largest zone.

Pressure limits

Hunter Industries and CSU Extension give the same ceilings: 80 PSI for rigid PVC and 50 PSI for polyethylene (flexible black) pipe. Hunter adds that the pressure must stay below the rating of the weakest part on the zone, so check valves, heads and swing joints too. Set the compressor's regulator before you open the valve, not after. More pressure does not clear water faster; more volume does.

What each compressor actually does

A compressor that cannot match the zone's flow still works, if you let its tank do the heavy lifting. Starting full and blowing a 10 GPM zone at 50 PSI:

Blowing a 10 GPM zone at 50 PSI, from a full tank
CompressorPump (SCFM at 90 PSI)Full flow from the tankThen, share of design flowRefill time
6 gallon pancake2.6100 s44 percent2.1 min
20 gallon49.7 min68 percent4.5 min
30 gallon5.129.6 min87 percent4.5 min
60 gallon10.5continuous100 percent5.2 min

The pump's rating at 90 PSI is a floor here: at 50 PSI the same pump delivers somewhat more, so the real figures are a little better. The pattern is what matters. A pancake moves the water at full flow for about 100 seconds, then needs about 2.1 minutes to refill from 50 PSI. Use it that way: close the compressor valve, let the tank fill, open the zone and blow until the heads spit mist, and repeat. Hunter recommends two or three short cycles per zone over one long one anyway, and warns against blowing dry pipe for long, since the friction heats it.

Irrigation contractors use towable compressors of 80 to 100 CFM or more, which Hunter recommends for any mainline of 2 in or less. They clear a zone in a couple of minutes and move on. A homeowner with one system and an afternoon does not need that; a 60 gallon machine matches a 10 GPM zone outright, and a 20 or 30 gallon one comes close. For another flow or tank, the tank size and runtime calculator gives the burst length.

Before you start

  • Wear eye protection and do not stand over heads, valves or pipe while the system is under air (Hunter).
  • Connect after the backflow preventer, never through it, and drain the backflow separately.
  • Start with the zone highest and furthest from the compressor and work back toward it.
  • Keep a zone open whenever air is connected, so the pipe is never pressurized with nowhere to go.

Frequently asked questions

Can I use a pancake compressor to blow out sprinklers?
Yes, with patience. A 2.6 SCFM pancake pushes a 10 GPM zone at full flow for about 100 seconds from a full tank, then needs about 2.1 minutes to refill. Blow each zone in several short bursts.
How many CFM do I need to blow out sprinklers?
Enough free air to match your largest zone's flow: about 5.9 SCFM for a 10 GPM zone at 50 PSI. Divide GPM by 7.5 for the air volume, then multiply by the absolute pressure ratio, which is what the table does.
What PSI should I use to blow out my sprinklers?
No more than 80 PSI for PVC pipe and 50 PSI for polyethylene, and below the rating of the weakest part on the zone. Volume clears water, not pressure.
Will a 20 gallon compressor blow out sprinklers?
Yes for a 10 GPM zone. A 20 gallon at 4 SCFM blows a 10 GPM zone at full flow for about 9.7 minutes from full, then delivers about 68 percent of the flow.
Is a 6 gallon compressor big enough to winterize sprinklers?
For small zones and short bursts. Its tank stores about 5.5 cu ft of free air between 150 and 50 PSI, about 100 seconds of full flow on a 10 GPM zone.
How long do you blow out each sprinkler zone?
Until no water comes out of the heads, about two minutes per zone on a contractor-size compressor according to Hunter, in two or three short cycles rather than one long one. Stop once the zone runs dry.
What size compressor do irrigation companies use?
Towable compressors delivering 80 to 100 CFM or more, which Hunter Industries recommends for mainlines up to 2 in. They clear a zone fast; a homeowner trades that speed for time.

Work it out for your own project